CO2 Gas detector for Duct application, CDS2000
CO2 Gas detector for Duct application: 0- 2000ppm
Specification
- Gas detected : Carbon dioxide (CO2)
- Sensing method : NDIR (Non-dispersive infrared)
- Detect range : 0 ~ 2,000ppm
- Accuracy : ±30ppm ±5% of measured value
- Warm-up time : Within 2 minutes
- Power supply : 24Vac, 24Vdc±20%, 50/60Hz
- Sensor life : >10 years
- Maintenance interval : not required
- Analog output : 0~10Vdc(default) or 0~20mA (selectable by jumper setting)
- Alarm output : SPST relay, normally open, 1A/120Vac, 1A/24Vdc contact rating, : activated at greater than 1000ppM, deactivated at less than 900ppM
- Response time : Within 120 sec (90% step)
- Protection class : IP63
- Operating temperature : 0 ~ 50℃
- Operating Humidity : 0 ~ 95%RH (non condensing)
- Storage temperature : -20 ~ 60℃
- Storage Humidity : 0 ~ 95%RH (non condensing)